RTHB機組UCP2設(shè)定調(diào)整記錄
|
OPERATOR SETTINGS GROUP 操作人員設(shè)定組:
|
|
|
Menu Item
顯示項目
|
Choices
選擇范圍
|
Default
出廠默認值
|
Setting
設(shè)定值
|
1
|
Front Panel Chilled Wtr Setpt:
操作面板冷凍水設(shè)定值
|
0->65 Deg F, -17.8->18.3 Deg C
|
44.0 Deg F, 6.7 Deg C.
|
|
2
|
Front Panel Current Limit Setpt:
操作面板電流限制設(shè)定值
|
40->100%
|
100%
|
|
3
|
Chilled Water Reset Type:
(If set to "Return" or "Outdoor Air", please refer to manual for setting procedure)
冷凍水復(fù)位類型: (如設(shè)定為`回水`或
`室外溫度`,請參閱手冊中設(shè)定程序)
|
Disable, Return, Constant Return, Outdoor Air
無效,回水,固定回水,室外溫度
|
Disable
無效
|
|
4
|
Ice Building:
制冰功能:
|
Disable, Enable
無效,有效
|
Disable
無效
|
|
5
|
Panel Ice Termination Setpoint:
(Displayed if Ice Building Enabled)
操作面板制冰完成設(shè)定點
(制冰功能有效時顯示此項目)
|
20->32 Deg F, -6.7->0. Deg C
|
27 Deg F. -2.8 Deg C.
|
|
6
|
Ice to Normal Cooling Timer
(Displayed if Ice Building Enabled)
制冰功能轉(zhuǎn)換正常制冷間隔時間
(制冰功能有效時顯示此項目)
|
0-10 Minutes
0-10 分鐘
|
5 Minutes
5 分鐘
|
|
7
|
Chilled Water Setpoint Source:
冷凍水設(shè)定點來源:
|
Front Panel, Tracer, Remote Computer, External Source, External Direct Capacity Cnt操作面板,Tracer,遠端
計算機,外部設(shè)定源,外部直接容量控制
|
Front Panel
操作面板
|
|
8
|
Current Limit Setpoint Source:
電流限制設(shè)定點來源:
|
Front Panel, Tracer, Remote Computer, External Source
操作面板,Tracer,遠端計算機,
外部設(shè)定源,
|
Front Panel
操作面板
|
|
9
|
Ice Termination Setpoint Source:
(Displayed only if "Ice Building Option" is installed) )制冰完成設(shè)
定點來源(制冰功能有效時,顯示)
|
Front Panel, Tracer, Remote Computer
操作面板,Tracer,遠端計算機,
|
Front Panel
操作面板
|
|
10
|
Setpoint Source Override:
設(shè)定點優(yōu)先來源
|
None, Use F.P Setpoints, Override Tracer, Use Default Setpoints
無, 操作面板, Tracer優(yōu)先, 默認設(shè)定值
|
None
無
|
|
SERVICE SETTINGS GROUP BASIC維修基本設(shè)定組:
|
|
Menu Item
顯示項目
|
Choices
選擇范圍
|
Default
出廠默認值
|
Setting
設(shè)定值
|
1
|
Language :
語言
|
English, Francais, Deutsche, Espanol, Nippon, Italiano, Dutch, Chinese
英語,法語,德語,西班牙語,中文,等等
|
English,Chinese
英語,中文
|
|
2
|
Display Units: 顯示單位制
|
English, SI英制單位,國際單位
|
English英制單位
|
|
3
|
Decimal Places Displayed:
顯示精度
|
XXX.X, XXX
|
XXX.X
|
|
4
|
Display Menu Headings:
顯示菜單題目
|
Enable, Disable
有效,無效
|
Enable
有效
|
|
5
|
Differential To Start Setpoint:
啟動溫差設(shè)定
|
1->10 Deg F, .5->5.5 Deg C
|
5 Deg F
|
|
6
|
Differential To Stop Setpoint:
停機溫差設(shè)定
|
1->10 Deg F, .5->5.5 Deg C
|
5 Deg F
|
|
7
|
Evap Pump Off Delay:
冷凍水泵延時停止設(shè)定
|
1->30 Minutes
1~30 分鐘
|
1 Minute
1分鐘
|
|
8
|
Clear Restart Inhibit Timer
再啟動禁止計時器清零操作
|
to Clear
按清除
|
|
|
FIELD STARTUP GROUP現(xiàn)場啟動組:(++--++):
|
|
Menu Item
顯示項目
|
Choices
選擇范圍
|
Default
出廠默認值
|
Setting
設(shè)定值
|
1
|
ICS Address: ICS地址
|
0 -> 255
|
65
|
|
2
|
Power Up Start Delay Time供電后延時啟動設(shè)定
|
0-600 Seconds0-600秒
|
0 Seconds0秒
|
|
3
|
Design Delta Temp Setpoint:冷凍水進/出水設(shè)計溫差
|
4 -> 30 Deg F, 2.2 -> 16.7 C
|
10 Deg F. 5.5 Deg C
|
|
4
|
Lvg Wtr Temp Cutout Setpoint:
(When this setpoint is within 1.7 Deg F of the Front Panel Chilled Water Setpoint, the Front Panel Chilled Water Setpoint is increased along with this setpoint to maintain the differential)低冷凍水出水溫度切斷設(shè)定點,(出水溫度設(shè)定點應(yīng)與低水溫切斷點保持1.7F溫差)
|
-10 -> 36 F, -23.2 -> 2.2 C
|
35 Deg F, 1.67 Deg C
|
|
5
|
Low Rfgt Temp Cutout Setpt:
(When this setpoint is within 6 Deg F of the Front Panel Chilled Water Setpoint, the Front Panel Chilled Water Setpoint is increased along with this setpoint ot maintain the differential.)低制冷劑飽和溫度切斷設(shè)定點,(出水溫度設(shè)定點應(yīng)與低制冷劑溫度切斷點保持6F溫差)
|
-35 -> 36 F, -37.2 -> 2.2 C
|
28 Deg F, -2.2 Deg C
|
|
6
|
Condenser Limit Setpoint:冷凝器壓力過高限制設(shè)定點
|
80 -> 120 %
|
93 %HPC
|
|
7
|
Maximum RI Timer Setiing:
最大再啟動禁止計時器設(shè)定
|
5 -> 20 Minutes
5~20分鐘
|
5 Minutes
5分鐘
|
|
8
|
Under/Over Voltage Protection:
(Permits "Enable" only if Option Installed)
過電壓/低電壓保護功能,(電壓傳感器已安裝時,有效)
|
Disable, Enable
無效,有效
|
Enable
有效
|
|
9
|
Phase Reversal Protection:反相保護功能
|
Disable, Enable無效,有效
|
Enable有效
|
|
10
|
Phase Unbalance Protection:相不平衡保護功能
|
Disable, Enable無效,有效
|
Enable有效
|
|
11
|
Momentary Power Loss Protection:
瞬時失電保護功能
|
Disable, Enable
無效,有效
|
Enable
有效
|
|
12
|
High Discharge Temp Cutout:
排氣溫度過高切斷設(shè)定點
|
170 ->220 F, 76.6 -> 104.4 C
|
190 Deg F,
87.8 Deg C
|
|
13
|
Soft Load Control: 軟加載控制功能
|
Disable, Enable無效,有效
|
Disable無效
|
|
14
|
Soft Load Starting Current Limit:
軟加載控制啟動電流限制
|
40 -> 100 %
|
100 %
|
|
15
|
Soft Load Current Limit Rate:
軟加載控制啟動電流限制速率
|
0.5 -> 5.0 % / Minute
0.5~5.0%/分鐘
|
5.0 % / Minute
5.0%/分鐘
|
|
16
|
Soft Load Lvg Water Rate:
軟加載控制冷凍水出水溫度速率
|
0.5 -> 5.0 Deg F/Minute
0.3 -> 2.8 Deg C/Minute
0.5~5.0F/分鐘 0.3~2.8C/分鐘
|
2.5 Deg F/Min
1.4 Deg C/Min
2.5F/分鐘1.4C/分鐘
|
|
17
|
LWT Proportional Gain Setpt:
冷凍水出水溫度比例增益設(shè)定
|
0-100% /F (0-180%/C)
|
*****
|
|
18
|
LWT Integral Gain Setpt:
冷凍水出水溫度積分增益設(shè)定
|
0-1%/F, (0-1.8%/C)
|
*****
|
|
19
|
LWT Derivative Gain Setpt:
冷凍水出水溫度微分增益設(shè)定
|
0-1000 %/F, (0-1800 %/C)
|
0.0 %/F, 0.0 %/C
|
|
20
|
EXV MAXIMUM Travel Setpt:
電子膨脹閥最大行程設(shè)定:
|
0 -> 20,000 (1 Step/Incr)
|
*****
|
|
21
|
EXV Closed Stop: 電子膨脹閥關(guān)閉設(shè)定點
|
0-100%
|
*****
|
|
22
|
EXV Open Stop: 電子膨脹閥打開設(shè)定點
|
0-100%
|
100%
|
|
23
|
EXV Deadband: 電子膨脹閥控制死區(qū)設(shè)定點
|
0-100Steps
|
20Steps
|
|
24
|
EXV Error Deadband:
電子膨脹閥控誤差死區(qū)設(shè)定點
|
0-2.00F
|
1.00F
|
|
25
|
Disch Supht Proportional Gain:
排氣過熱度比例增益設(shè)定
|
0-200
|
4
|
|
26
|
Disch Supht Integral Gain Setpt:
排氣過熱度積分增益設(shè)定
|
0-200
|
*****
|
|
27
|
Disch Supht Derivative Gain Setpt:
排氣過熱度微分增益設(shè)定
|
0-150
|
*****
|
|
28
|
Extended Unloading擴展卸載
|
Enable, Disable, 有效,無效,
|
Disable無效
|
|
29
|
Extended Unload Time
擴展卸載限制時間
|
Enable, Disable, 有效,無效,
Unlimited Time不限制時間
|
Disable
無效
|
|
30
|
Maximum Extended Unloading Time
擴展卸載的時間
|
1-480 Min
|
30 Min
|
|
31
|
Local Atmospheric Pressure:
當?shù)卮髿鈮毫?/span>
|
10 -> 15 psia
10~15Psia
|
14.7 psia
14.7 Psia
|
|
MACHINE CONFIGURATION GROUP機組配置組:(+-+-+-):
|
|
Menu Item
顯示項目
|
Choices
選擇范圍
|
Default
出廠默認值
|
Setting
設(shè)定值
|
1
|
Unit Frequency:
機組適用頻率
|
60 HZ, 50 HZ
|
60 HZ
|
|
2
|
Unit Type:
機組類型
|
CVHE,CVHG,RTHB
|
RTHB
|
|
3
|
Unit Tons:
機組制冷量(冷噸)
|
100 ->1800 ( 10 Ton incr)
|
500
|
|
4
|
Refrigerant Type:
使用制冷劑類型
|
R11, R123, R12, R134a, Water. R22
|
R22;R134a
|
|
5
|
Starter Type:
啟動器類型
|
Undefined, Variable Speed,
Y-Delta, X-Line, Solid State,
Auto Xformer, Primary Reactor不明確,變速啟動,星-三角啟動,直接啟動,固態(tài)啟動
自藕變壓器啟動,初級電抗器啟動
|
Y-Delta
星-三角啟動
|
|
6
|
2nd Level Contactor Integrity Test:
(Startup Contactor Test--Y-D Only)
第二級接觸器完整性測試(只適用星-三角啟動)
|
Disable, Enable
無效,有效
|
Disable無效
Enable 有效
(星-三角啟動)
|
|
7
|
Rated Load Amps: 額定運行電流
|
0 -> 2,500
|
300
|
|
8
|
Motor Heating Constant: 馬達發(fā)熱時間
|
0 - 100 Minutes0~100分鐘
|
5 Minutes5分鐘
|
|
9
|
Current Overload Setting # 1:
(See Manual for Setup Procedure)
電流過載設(shè)定#1(參見手冊啟動程序)
|
00 -> 31
|
00
|
|
11
|
Current Overload Setting # 2:
(255 Minus Timer Setpt #1 above)
電流過載設(shè)定#2=255減10項設(shè)定值
|
224 -> 255
|
255
|
|
12
|
Maximum Accel Timer Setpt #1:
(See Manual for Recommended Setpt)
啟動最大加速時間設(shè)定#1(參見手冊建議值)
|
2 -> 64 Seconds
|
27 Seconds
|
|
13
|
Maximum Accel Timer Setpt #2:
(255 Minus Timer Setpt #1 above)
啟動最大加速時間設(shè)定#2=255減12項設(shè)定值
|
191 -> 253 Seconds
|
228 Seconds
|
|
14
|
(Opt)External Chilled Wtr Setpoint:
外部冷凍水出水溫度設(shè)定點輸入
|
Installed, Not Installed
已安裝,未安裝
|
Not Installed
未安裝
|
|
15
|
(opt)External Current Limit Setpt:
外部電路限制設(shè)定點輸入
|
Installed, Not Installed
已安裝,未安裝
|
Not Installed
未安裝
|
|
16
|
Acceleration Time Out Action:
啟動加速超時
(Recommend "Shutdown" Only)
(只推薦設(shè)定為`停機`)
|
Shutdown, Transition
停機,轉(zhuǎn)換
|
Shutdown
停機
|
|
19
|
Motor Winding RTD Type:
馬達線圈溫度傳感器類型
|
75 Ohm/ 75 F,100 Ohm/ 0 C
75歐姆/75F 100歐姆/0C
|
75 Ohm / 75 Deg F
75歐姆/75F
|
|
20
|
High Pressure cutout setting:
高壓切斷設(shè)定點
|
0 ->500 PSIG (5 PSIG incr)
|
270 PSIG
|
|
21
|
Line Voltage Sensing Option:
線電壓傳感器選裝功能
|
Installed, Not Installed
已安裝,未安裝
|
Not Installed
未安裝
|
|
22
|
Unit Line Voltage
機組電壓
|
180-6600 Volts,(5V / Incr)
180-6600伏
|
380 Volt
380伏
|
|
23
|
Ice Building Option:
制冰選裝功能
|
Installed, Not Installed
已安裝,未安裝
|
Not Installed
未安裝
|
|
24
|
External Analog Inputs:
外部模擬信號輸入類型
|
4-20 ma, 2-10 vdc
|
4-20 ma
|
|
25
|
Tracer Option:
Tracer自控選裝功能
|
Installed, Not Installed
已安裝,未安裝
|
Not Installed
未安裝
|
|
26
|
TCI Option:
TCI 模塊選裝
|
Installed, Not Installed
已安裝,未安裝
|
Not Installed
未安裝
|
|
27
|
Printer Option:
打印模塊選裝
|
Installed, Not Installed
已安裝,未安裝
|
Not Installed
未安裝
|
|
SERVICE TEST GROUP維修測試組:(++--++):
|
|
Menu Item
顯示項目
|
Choices
選擇范圍
|
Default
出廠默認值
|
Setting
設(shè)定值
|
1
|
Chilled Water Pump:
冷凍水泵控制
|
Auto, On
自動,開
|
Auto
自動
|
|
2
|
Chilled Water Flow Switch:
冷凍水流量開關(guān)
|
FS Open/No Flow,
流量開關(guān)斷開/無流動 FS Closed/Flow
流量開關(guān)閉合/流動
|
|
|
3
|
Condenser Water Pump:
冷卻水泵控制
|
Auto, On
自動,開
|
Auto
自動
|
|
4
|
Condenser Water Flow Switch:
冷卻水流量開關(guān)
|
FS Open/No Flow,
流量開關(guān)斷開/無流動 FS Closed/Flow
流量開關(guān)閉合/流動
|
|
|
5
|
Starter Dry Run:
(See Manual for Procedures --Y-D only)
干(無電源)運行測試啟動器
(參見手冊中有關(guān)程序—只適用星-三角啟動器)
|
|
|
|
6
|
Expansion Valve Test:
膨脹閥測試
|
Enable, Disable,
無效,有效,
|
Disable
無效
|
|
7
|
EXV control Status
電子膨脹閥控制狀態(tài)
|
Auto, Manual
自動,手動
|
Auto
自動
|
|
8
|
Expansion Valve Position:
膨脹閥位置
|
XXX.X% Open
XXX.X%開
|
|
|
9
|
Discharge Superheat
排氣過熱度
|
XXX.X F/C
|
|
|
10
|
Slide Valve Control Status:
滑閥控制狀態(tài)
|
Auto, Hold, Load, Unload
自動,保持,加載,減載
|
|
|
11
|
Limit Condition
限制狀態(tài)
|
|
|
|
12
|
Manual Load/Unload Duty Cycle
手動加載/減載循環(huán)
|
0-50%
|
30%
|
|